1.6 Positioning the stove
Distance to walls and lintel
When the stove is positioned near combustible materials, observe all current local and national
building regulations with regards to clearances. Whatever regulations apply to your area, do
not in any case install the stove within 8 inches of combustible materials around the sides or
16 inches above the top of the stove (fireplace installations require greater clearances above
the stove - see below in the clearance chart). These distances may need to be increased if the
materials are sensitive to heat. Note also that wall paper and other decorative materials may
become detached with the effects of heat and care should be taken to ensure that they do not
fall towards the stove in such an event.
When the stove is positioned near non-combustible materials, a gap of 4 inches or more is
recommended for cleaning purposes and to ensure that heat circulates around the stove and
out into the room.
CLEARANCE REQUIREMENTS STANDARD RESIDENTIAL INSTALLATION
SINGLEWALL CONNECTOR
USA CANADA
A.
B.
C.
D.
E.
F.
G.
H.
22’’
20’’
16’’
31’’
22’’
25’’
-
-
560 mm.
510 mm.
405 mm.
785 mm.
560 mm.
635 mm.
-
-
SIDEWALL TO UNIT
BACKWALL TO UNIT
CORNERWALL TO UNIT
SIDEWALL TO CONNECTOR
BACKWALL TO CONNECTOR
CORNERWALL TO CONNECTOR
UNIT TO CEILING
FLOOR TO CEILING
CLEARANCE REQUIREMENTS STANDARD RESIDENTIAL INSTALLATION
DOUBLEWALL CONNECTOR
USA CANADA
A.
B.
C.
D.
E.
F.
G.
H.
20’’
16’’
14’’
-
-
-
-
-
510 mm.
405 mm.
355 mm.
-
-
-
-
-
SIDEWALL TO UNIT
BACKWALL TO UNIT
CORNERWALL TO UNIT
SIDEWALL TO CONNECTOR
BACKWALL TO CONNECTOR
CORNERWALL TO CONNECTOR
UNIT TO CEILING
FLOOR TO CEILING
CLEARANCE REQUIREMENTS STANDARD RESIDENTIAL INSTALLATION
FIREPLACE HEARTH INSTALLATION
(ALCOVE)
USA CANADA
A.
B.
C.
D.
E.
F.
19’’
31’’
27’’
18’’
-
-
485 mm.
790 mm.
685 mm.
460 mm.
-
-
SIDEWALL TO UNIT
COMBUSTIBLE MANTEL TO UNIT
TOP FACING
SIDE FACING
HEARTH EXTENDING, FRONT
HEARTH EXTENDING, SIDE
FLOOR PROTECTION REQUIREMENTS NON-COMBUSTIBLE MATERIALS
BENEATH STOVE
USA CANADA
A.
B.
C.
D.
-
6’’
6’’
16’’
200 mm.
200 mm.
200 mm.
450 mm.
EXTENDING DISTANCE, BACK
EXTENDING DISTANCE, RIGHT SIDE
EXTENDING DISTANCE, LEFT SIDE
EXTENDING DISTANCE, FRONT
FLOOR PROTECTOR MUST BE NON-
COMBUSTIBLE MATERIAL, WITH AN R-VALUE
OF 1.0.
IT MUST EXTEND BENEATH HEATER AND TO
THE FRONT/SIDES/REAR AS INDICATED